INSTALLATION INSTRUCTIONS
Cont...
9
INSTALLATION INSTRUCTIONS
Cont...
RESTRICTOR PLACEMENT “FOR ABOVE 7 FOOT VERTICAL RISE VENTED
APPLICATIONS ONLY”
Vertical Venting between Seven Feet (7’) and Ten Feet (10’)
requires Restrictor Number 1 as per the Venting Chart on
page 8.
Simpson Duravent
Archgard System
Archgard System
In the Archgard system the restrictors are placed on the exhaust outlet on the appliance.
Simpson Duravent
With Simpson Duravent locate the restrictor in the exhaust section fitting into the formed lip.
Restrictor Placement
WARNING:
These restrictors are only to be installed in the vent system if the vent exceeds 7’
in vertical height, *Restrictor Number 1 below is required.
Installing them
under any other circumstances may cause hazardous venting conditions
and may result in personal injury, property damage or death.
NOTE:
Vent restrictors are designed to reduce vertical stack action for above 7 feet (7’),
which will reduce the velocity of incoming combustion air and not adversely affect the standing
pilot or the flame of the appliance.
9