SunTouch P-3285 DualTemp Digital Outdoor Instructions 

24v for use with CP ContactorPro Panels (CP-50/100/200) 

 

To enter the parameter menu, press and hold the 

OK 

button for 5 seconds. 

  Use the +/- keys to select the installation parameter to be adjusted.  

 Press 

OK 

to toggle the parameter setting or to edit its value.   When the value begins to blink, use the 

+/- keys to adjust its value.   Press OK to select the adjusted value. 

  Toggle to “End” and press OK to exit the installation parameter menu. 

 Parameters 

(Only 

Bold 

apply to Outdoor Patio Heating)

 

 

J0: °C/°F Temperature display section

 

J1: Hot

/Cold regulation mode. Select Hot for Heating, Cold for cooling. 

 

Cy: Proportional Integral regulation time cycle, value in minutes (default: 15 minute cycle). 

 

bp: Proportional Integral regulation band amplitude value in degrees °C/°F (default: 2.0°C/3.6°F). 

 

J4

: NO/

NC

 Normally Open or Normally Close actuator selection. 

ƒ

 

NC: If using an isolation relay and/or a relay box. 

ƒ

 

NO: if connecting to a Watts Zone Valve control. 

 

J5: Select PMP (Pump Maintenance Program) to perform a 1 minute exercise every day. 

 

J6

:

 Air: Air (room) setpoint. Displays air temperature with floor low (FL) and high (FH) limits. 

ƒ

 

Flr:  Floor (external sensor) setpoint. Displays floor temperature 
without floor low/high limits. Air temperature is not a control 
boundary. 

Î

 

Air temp is not used because the T-stat is mounted INSIDE and the 
area to be monitored is OUTSIDE and monitored with Floor Sensor 
Only 

 

J7: rEG (proportional Integral) or HYs (0.3°C Hysteresis) regulation type selection. 

 

Cp: Proportional Integral regulation temperature compensation value in °C/°F 

 (default: 

2.0°C/3.6°F). 

 

Ao: Air Sensor offset adjustment (default: no offset), display measure air sensor value. 

 

Fo: Floor sensor offset adjustment (default: no offset), display measure floor 

 sensor 

value. 

 

FL: Floor temperature LOW limitation (default: 5°C/41°F), effective only if floor 

 

sensor present and set J6 to Air. 

 

FH: Floor temperature HIGH limitation (default: 28°C/82°F), effective only if floor 

 

sensor present and set J6 to Air. 

 

CLr: Press OK to reset to factory defaults. 

 

End: Press OK to exit installation parameters. 

 

 