890557_d•en•01.07.2014
We reserve the right to carry out improvements
38
Wisotronic 1-channel
Operating instructions
7.2.1.1 Sun control OA/OFF
Set or delete the checkmark in the [
Sun control ON/OFF
] line to activate or
deactivate the sun control.
The [
Stand.
] function button sets the channel-dependent factory setting.
7.2.1.2 Limit value SAA
The value "SUN" specifies from which brightness the sun shading product of
this channel shall be lowered. The setting range is 3...100 klx.
Turn the touch wheel to set the "SUN" limit value.
7.2.1.3 elay SAA
To prevent the sun shading product from being immediately lowered at each
brightness change (e.g. when the sun temporarily shines through an oth-
erwise thick cloud cover), a delay time can be assigned to the "SUN" limit
value. This quiets the motion behaviour of the sun shading product, thereby
increasing the level of comfort.
When the limit values are reached or exceeded for the duration of this delay
time, a move command is triggered and the sun shading product is moved
to the set position and slat angle. The setting range is 0...99 minutes.
Turn the touch wheel to set the value for the "SUN" delay.
A setting of “0 min.” deactivates the delay, the function button [
Stand.
] sets
the factory setting).
7.2.1.4 Position SAA
The "SUN" position value specifies the position to which a sun shading
product is to be lowered in case of sunshine. The setting range is 0-100%; a
value of 0% corresponds to the upper limit position and a value of 100% to
the lower limit position.
Turn the touch wheel to set the "SUN" limit value.
The function button [
---
] leaves the position unchanged; function button
[
Stand
.] sets the value to the factory setting.
7.2.1.5 Slat angle SAA
This setting is required when you have chosen a slat product (external or
internal venetian blinds) for the channel type. If you have connected a slat
product (such as external venetian blinds), you can specify the position of the
slats after they are lowered. This is especially useful if you prefer a specific
setting. In addition, you do not have to tilt the slats up after the product
descended automatically. The sun control automatically tilts up the slats if
programmed accordingly.
The factory setting for the slat position with automatic operation is 38°.
Sun control