6.3.8 Fault alarm contact
For the activation of signal lamps or acoustic alarms and for notification of
higher level central control units, a channel can be parameterised as a fault
alarm contact.
The fault alarm contact is activated when:
The operating voltage fails (immediately)
The power unit fails (immediately)
There is no communication with the weather station (after 3 min.)
There is no communication with the control panel (after 40 min.)
When de-energised (idle state) and if there is a fault, the contact between C
and E is closed. When there is no fault, the relay pulls in and closes the con-
tact between C and
.
Each channel of the Wisotronic can be used as a fault alarm contact.
During commissioning, this channel must be created for the product fault
alarm contact.
The push button inputs of the channel parameterised as a fault alarm contact
are without function.
Wisotronic
power unit
F2
F1
F3
F4
1
9 8 7 6
4 3 2 1
4 3 2 1
4 3 2 1
N
L
PE
Red (fault)
Green (OK)
Fig. 25
Fault alarm contact connection
Terminal blocks X2, X3, X4
Permissible line cross section
0.2 to 2.5 mm
2
single-wire
0.2 to 2.5 mm
2
fine wire
Stripping length
6.5 mm
Connection