6.3.4 Sun shading drives
The Wisotronic can directly control mains-supplied drives. Simultaneously,
other channels can be used to activate SELV drives via motor control units
(e.g. 24 V drives via MSE Inside).
Wisotronic
power unit
F2
F1
F3
F4
9 8 7 6 5 4 3 2 1
9 8 7 6
4 3 2 1
4 3 2 1
4 3 2 1
1
1
2
2
3
3
3
2
1
GNYE
BU
BK
BN
M1
~
Motor 1
H05RR-F 4 G 0.75 BK
1
1
2
2
3
3
3
2
1
GNYE
BU
BK
BN
M1
~
Motor 2
1
1
2
2
3
3
Plug-and-socket connection
3
2
1
GNYE
BU
BK
BN
M1
~
Motor 3
PE
N
L1
NYM-J 3x1.5
Supply line
100-240 V AC
50/60 Hz / 16A
Only one drive may be
connected per channel.
Parallel connection of
multiple drives will
damage the motor.
Example for actuation of
motor control units with
downstream SELV or
230-V drives
C/P/+
Fig. 21
Connection of sun shading drives
Terminal blocks X2, X3, X4
Permissible line cross section
0.2 to 2.5 mm
2
single-wire
0.2 to 2.5 mm
2
fine wire
Stripping length
6.5 mm
WARNING
When mixing channels with mains and SELV power circuits, the
regulations for SELV circuits specified in VDE 0805 or EN 60950 must be
adhered to.
Connection