WAREMA KNX SA Series Скачать руководство пользователя страница 1

1

warema_2016157_alhb_en_v3•2022-03-01

We reserve the right to make technical modifications

ARNING

W

 

It is important to comply with the following 

points in the interest of personal safety.

 

 

Children may not play with the operating elements of 

the control unit or the remote control. Store remote 

controls out of reach of children.

 

 

Make sure that no persons or objects are in the range 

of movement of the driven parts (blinds, external vene-

tian blinds, etc.).

 

 

Disconnect the device from the operating voltage if 

cleaning or other maintenance work must be per-

formed.

Function of the sun shading actuator

You will find a detailed description of the software func-

tions for the KNX  sun shading actuators in the manual 

(art. no. 2014 787). You can download the manual and 

the product database of the sun shading actuator from 

www.warema.com.

Installation

Insert a slotted screwdriver (recommendation: 3.0 - 

4.0 mm blade) into a cover opening (Fig. 3) and carefully 

pry open the hinged cover. Repeat the procedure for the 

second opening of the cover. After both latches have been 

unlatched,

the cover can be removed. Open the second cover in 

the same way. Alternatively, the AP model may also be 

mounted on a DIN rail (TH 35-15). 

Electrical connection

An on-site overload current protection device (fuse) and a 

disconnecting and isolating switch to switch off the entire 

system must be provided.
The electrical connection is made as shown in the wiring 

diagram on the reverse side (Fig. 4), the connection to 

the KNX bus system and the drives is made using spring 

terminals, the connecting lines are designed as screw 

terminals. 

ARNING

W

 

All terminals and connections under cur-

rent must be covered completely against 

touching by the latched cover. It should not 

be possible to open the latched cover with-

out using tools.

General information

Fig. 1 

KNX SA 8M230.16 AP

The KNX SA 2/4/6/8M230.x AP sun shading actuator is a 

device for the central operation of up to eight sun shad-

ing drives 230 V AC (the following uses the sun shading 

actuator for eight motors with 16 push button inputs as an 

example).

The device is operated using a KNX bus system. The 

drives and the motor control unit are supplied via a 

230 V AC control line.

Intended use

The KNX SA 2/4/6/8M230.x AP was developed to control 

sun shading products. The approval of the manufacturer 

must be obtained for any use of the device other than its 

intended purpose specified in these instructions.

Safety instructions

ARNING

W

 

The electrical installation (assembly)/

dismantling must be performed by a cer-

tified electrician in accordance with the 

electrical installation regulations published 

by the Association of German Electrical 

Engineers (VDE 0100) or the standards and 

legal requirements of the country in which 

the device is being installed. The electri-

cian must observe the installation instruc-

tions included with the supplied electrical 

devices.

ARNING

W

 

If hazard-free operation cannot be 

assumed, the device may not be started or 

must be deactivated. This assumption is 

justified if:

 

  the housing or the connecting lines show signs of 

damage, 

 

  the device is no longer working.

Installation instructions

KNX SA 2/4/6/8M230.x AP 

Valid from  

1 March 2022

Keep for future use.

Содержание KNX SA Series

Страница 1: ...the drives is made using spring terminals the connecting lines are designed as screw terminals ARNING W All terminals and connections under cur rent must be covered completely against touching by the latched cover It should not be possible to open the latched cover with out using tools General information Fig 1 KNX SA 8M230 16 AP The KNX SA 2 4 6 8M230 x AP sun shading actuator is a device for the...

Страница 2: ...ut the device into programming mode The red LED lights up when programming mode is active Programming is performed using the ETS on the PC This software ends the programming mode automatically The red LED goes out If the programming mode is to be ended earlier press the programming button again The red LED goes out Fig 2 View of the keypad Maintenance There are no parts inside the device that requ...

Страница 3: ... Frel Degree of soiling 2 Connection Connecting line Screw terminals KNX bus system drives push button inputs Spring terminals Wire cross sections Connecting line max 2 5 mm KNX bus system 0 6 0 8 mm Motor outputs push but ton inputs max 1 5 mm Housing Degree of protection Surface mounted housing IP30 Safety class PE is looped through I Miscellaneous Conformity can be viewed at www warema de ce Th...

Страница 4: ...3 2 N M4 1 PE N PE M4 2 M5 1 M5 2 N M6 1 PE N PE M6 2 F1 6 3 AT H 6 3 AT H 2 3 1 M Motor 7 sun shading system 2 3 1 M Motor 8 sun shading system N PE N PE M7 1 M7 2 N M8 1 PE N PE M8 2 F2 BU BK BN GNYE BU BK BN GNYE X2 X3 X4 All push button lines JY St Y 2x2x0 8 mm max line length 200 m for interference proof routing use a twisted paired line X5 In1 1 In In1 2 In2 1 In3 1 In4 1 In4 2 In3 2 In2 2 I...