Electrical Management Controller. 

 

Original Instructions 

 

Содержание WEX300

Страница 1: ...Product Manual WEX300 Electrical Management Controller OriginalInstructions ...

Страница 2: ...e can be used by persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved If the supply cord is damaged it must be replaced by Wallgate its service agents or similarly qualified persons in order to avoid hazard AS 1172 Certific...

Страница 3: ...e on attaching the unit 6 4 Product Summary 6 5 Product Specification 7 5 1 Supply 7 5 2 Digital Inputs 7 5 3 Digital Outputs 7 5 4 Relay Outputs 7 5 5 Monitoring and Safety 7 5 6 Communications 7 5 7 Updating and Programming 7 6 Connections 8 7 System Description 11 7 1 Digital Inputs Outputs and LEDs 11 7 2 Relay Outputs 12 7 3 Communications 12 7 4 Mains Voltage Devices 13 8 Data Logging 13 9 T...

Страница 4: ...anty will be invalidated if the equipment is installed or serviced by unqualified personnel No part of this publication and the information contained may be reproduced transmitted stored in a retrieval system used or disclosed wholly or partly without prior written permission from Wallgate Limited For full warranty details please see Wallgate Limited Terms and Conditions Please ensure this manual ...

Страница 5: ...list is used to give information that is not sequential 2 5 Tick Bullet lists A tick bullet list is used to imply a checklist of components or actions not sequential 2 6 Menu items Menu items submenu items and settings where available are given in bold 3 Installation and Commissioning 3 1 Package Contents Before beginning the installation make sure that you have the following items 1 WDC 200 NX El...

Страница 6: ...ons 1 Terminate the supply cable into the main supply breaker 2 Make sure that the input leads are plugged into the correct sockets 3 Complete electrical testing of the installation 4 Product Summary The WEX 300 electronic control units are designed to manage the operation of up to 12x Electrical Circuits The WEX 300 is used in conjunction with the WDC 200 NX Controller connected using the CAN Bus...

Страница 7: ... indicating status of inputs 5 4 Relay Outputs All relay outputs are to a maximum RCBO capability of 10A however please note the default lighting and mains RCBO s fitted are shown below 5 5 Monitoring and Safety 1 x Double Pole Main Isolation Breaker 2 x C4 RCBO for mains socket protection 2 x C2 RCBO for lighting protection NOTE The WEX300 can be specified with MAX 10A per Breaker please contact ...

Страница 8: ...o the peripherals it is controlling through 13 glands located on the top side of the housing One M25 gland for the incoming power and 12 M20 glands for the socket and lighting circuits Below in Figure 1 is an overview of the connections to the WEX300 unit Figure 1 Connection Overview ...

Страница 9: ...h circuit breaker CB1 in Figure 2 below A common Live bus is fed through RCBO 1 2 3 and 4 The neutrals are monitored by the power monitoring circuitry on PCB000378 WEX300 MTR through shunts PM1 PM2 PM3 and PM4 on the neutral lines of the RCBOs Figure 2 Internal Mains Wiring ...

Страница 10: ...s A1 circuit C Feed out to Socket A2 circuit D Feed out to Light A1 circuit E Feed out to Light A2 circuit F Feed out to Light A3 circuit G Feed out to Light A4 circuit H Feed in for Light A circuits from RCBO2 I Feed in for Socket B circuits from RCBO3 J Feed out to Sockets B1 circuit K Feed out to Socket B2 circuit L Feed out to Light B1 circuit M Feed out to Light B2 circuit N Feed out to Light...

Страница 11: ...denotes Jack 1 and the numbering follows this down to SKT20 which denotes Jack 20 in the configuration software The Tip of the 3 5mm jack is reserved for these input signals and the screen is grounded The Ring of the jack is reserved for the LED Digital outputs and are denoted as LED in the Configuration software these are for input status feedback The behaviour of the LEDs is displayed below in T...

Страница 12: ...r relays for lights this is displayed below in Figure 5 Neutral to all circuits is common and the Live is switched Figure 5 Relay Outputs Sections 7 3 Communications The WEX300 is a slave device and is controlled by a WDC100 200 via CANbus The CAN is connected via a 4way RJ11 connector Within the WEX300 there are three boards which also need to communicate the control board the metering board and ...

Страница 13: ...ent plate to avoid contact Take care to isolate the devices correctly when connections are being made 8 Data Logging Data logging records the events of all functionality The data logs are stored locally on the WDC 200 NX and can be exported to a PC or laptop The download data is in the form of a csv file and can be viewed via WDCMS or exported to an external database 9 Technical Specifications Pow...

Страница 14: ...14 WEX 300 Electrical Management Revision 2 ...

Страница 15: ...offer a comprehensive service package details of which can be obtained from our customer service department A spare parts service is also available The electronic control unit does not have any user serviceable parts In the event of a fault switch off the electrical supply and contact an authorised electrician to replace the unit Any service or repair work must be carried out by a qualified engine...

Страница 16: ...Wallgate Ltd Crow Lane Wilton Salisbury Wiltshire SP2 0HB England tel 44 0 1722 744594 fax 44 0 1722 742096 email service wallgate com web www wallgate com ...