24
WDC200-NX Electronic Water Management.
Revision-2
Using the
Log Activations
setting the Time Slots can be set to log when the Time
Slot disables or enables the WC, Shower, or Tap operation.
8.4 Inactivity Purge
The control unit can purge an output following pre-set periods of inactivity defined by
the Inactivity Period. This is a hygiene function that can be used to reduce the
possibility of water stagnating in the pipe work and the associated risks, it will also
reduce the possibility of waste traps drying / evaporating following periods of
inactivity. This functionality can be disabled using the Inactivity Purge setting.
8.5 Auto Run
The Auto Run function will operate the WC, Shower, or Tap automatically at the
times specified by the enabled schedules in the
Event Schedules
list. If the
Log
Activations
setting is Enabled the Auto Run will log every time it automatically
activates the WC, Shower, or Tap.
8.6 IR Walkaway
The IR Walkaway is designed to work with an infrared input sensor. When the user
has been in front of the IR sensor for more than the time specified in the
WC
Occupy Half Flush Time
setting, a half flush will be scheduled to run on the WC. If
the user remains for more than the time specified in the
WC Occupy Full Flush
Time
setting, a full flush will be scheduled to run on the W.C. When the user moves
away from the IR sensor the system will wait for the
Vacate Time
to pass before
activating the scheduled Half or Full flush action on the W.C.
8.7 Lockout
The Lockout function restricts the number of usages for the basin/bath, shower, WC,
etc.
The Lockout feature is disabled by default.
If the permitted number of operations exceeds the
Cycle Activations
within the
Cycle Period
for any item, the item is locked from use for the
Lockout Penalty
period of time. All parameters are fully adjustable. The lockout status is shown on the
WDC display, visible on the Front-End and can be linked to BMS for remote
monitoring.
To cancel the Lockout function when it has been activated due to excessive
operations and allow the unit to operate normally again, carry out the following steps:
(any one of these steps should be sufficient to cancel the lockout)
1
Cycle the power to the unit (lockouts are in volatile memory)
2
Clear lockouts via Quick Functions
3
Use an auxiliary input configured to ‘clear lockouts’