134
wallaceperimetersecurity.com
Phone: 866.300.1110
BI-PARTING GATE SYSTEMS
Bi-parting Gate Systems
Configuring two operators to be a Primary and Secondary pair is easy with the SmartDC Controller. There
is no need to order a special model or any adapters. The area of the board marked Dual Gate employs a
3-wire RS485 serial port for communication between primary and secondary operators. See Figure 34.
Power Requirements
When installing a dual-operator system, the following must be adhered to:
•
An electrical conduit for interconnecting wires must span between the two operators. The primary
-
secondary communication wires and any low voltage control wires must be installed in a conduit
that is separate from the high voltage power wires. See
“Figure 35. Primary and Secondary Wiring
�
•
Complete the installation of both operators as separate machines and verify that their basic functions
are correct as solo operators before interconnecting them.
•
External control inputs, vehicle detectors and entrapment protection sensors may be connected to
either gate operator without regard to preference.
•
Be sure both operators are running the same software version. The software version is available on
the display by pressing the RESET button on the operator
.
The software version appears beneath
the word HYSECURITY
.
Keep the most current software loaded. It is available at
. Make it part of your maintenance routine to check for software upgrades on a regular basis.
•
Both operators can be connected to the same 20A circuit breaker in the main panel. The wire size
affects operator performance. Use the following chart as a guideline to size wire for the given
distance from the power source to BOTH operators.
Figure 34
.
Dual Gate Primary/Secondary Connections
AC Power - Dual Operators 14-gauge wire
12-gauge wire
10-gauge wire
115V
460 ft (140 meters)
750 ft (228 meters)
1160 ft (354 meters)
230V
1465 ft (446 meters)
2350 ft (716 meters)
3750 ft (1143 meters)
Table 10. Wire Length Chart
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...