Alpha/Delta (Kinetic Operator) Installation and Maintenance Manual
Revision 1 - MAY 2023
129
USER RELAYS - PROGRAMMING PROCEDURE
User Relays - Programming Procedure
The SmartDC Controller is able to interface with many types of external devices through the use of two
user-programmable output relays. All of the user relay functions identified and described in Table 9 are
accessible in the Installer Menu.
The User Relays will operate normally
to less than 18VDC. The USER 2
RELAY is rated for DC only up to 48V
and does not have an N.C. (normally
closed) connection.
Use the SmartDC Controller buttons to program the user relays according to the following steps:
1.
Select and connect to the relay you wish to use on the SmartDC Controller board
�
2.
Access the Installer Menu and RL 1 or RL 2 display (depending on the relay you have connected).
3.
Enter the appropriate function using the associated number (1 through 45) listed in the table.
Table 9. User-Programmable User Relays - Function Options
No�
Name
Description
1
Close limit output
Creates an interlock signal to another operator’s interlock input, or
simply to indicate that the gate is secure. The relay is released when
the fully-closed limit switch is tripped. The relay is energized when the
fully-closed limit is released. (Any open command energizes the relay.)
2
Close limit pulse output
Used in a sequenced system to command a second machine to
close. Generates a brief pulsed output that occurs when the close
limit is triggered.
3
Open limit output
Indicates a full-open position. This output becomes active when an
open-limit is triggered and releases when the open-limit is released.
4
Open limit pulse output
Triggers a sequenced barrier arm gate operator to open. Generates
a brief pulsed-output when the open-limit is triggered. An
additional pulse is also generated with any new open command
even when the gate is already fully-opened.
Содержание ALPHA
Страница 36: ...36 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 38: ...38 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 40: ...40 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 42: ...42 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 44: ...44 wallaceperimetersecurity com Phone 866 300 1110 ALPHA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS ALPHA...
Страница 48: ...48 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 50: ...50 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 52: ...52 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 54: ...54 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 56: ...56 wallaceperimetersecurity com Phone 866 300 1110 DELTA GATE MODEL STEP BY STEP INSTALLATION DIAGRAMS...
Страница 167: ...Figure 47 Schematic for Kinetic DC 15 Kinetic 1 and Kinetic DC 10F Kinetic 2 Operator s...
Страница 168: ......
Страница 169: ...Figure 48 Schematic for Kinetic DCS 15 Kinetic 1S and Kinetic DCS 10F Kinetic 2S Solar Operator s...
Страница 170: ......
Страница 180: ......
Страница 182: ...115 Lowson Crescent Winnipeg Manitoba Canada R3P 1A6 Phone 866 300 1110 wallaceperimetersecurity com...