289.805.003
17
Date: 2018-11-28
Manual operation using the Control Box
Insert the control box (not included) into the limit switch connector and apply mains power to the
product.
Procedure:
State
Step Description
Setup/
Adjustment
1
Select mode 7 on the MODE switch and set a slow motor speed using the DMX
address switches, approx. 100 is recommended for setup purpose.
2
Push the Up (CW) button on the control box and keep it pushed until the desired
soft-limit top position is reached.
3
Push the Down (CCW) button on the control box and keep it pushed until the
desired soft-limit bottom position is reached.
4
Select mode 8 and set the desired speed using a value between 060 and 512 on
the DMX address switches (The minimum obtainable speed may vary due to the
weight of the load).
Operation
1
Push the Up (CW) button and the motor will move to the top position.
2
Push the Down (CCW) button and the motor will move to the bottom position.
Power
down
-
Return to the top position as this is always the expected position at power-on. In
case this is not followed, a full setup procedure will need to be done.
Power-on
-
Whenever the product is repowered, there should be no need to setup the top
and bottom positions, provided the product was powered down at the top
position, and the shaft position was not changed (manually or due to
transportation).
Control box and Hard-limit switch port
The following table shows the needed connections to the control box port for using the manual
mode, it also includes the connections for hard-limit switches when desired.
Pin Control box option
(mode 7 and 8)
Hard-limit switch option
(mode 4, 5 and 6)
Connector
LIMIT SWITCH
1
GND (COM/Common)
GND (COM/Common)
2
Down (CCW) control button input
(NO/normal open switch type)
CW(Up) hard-limit switch input
(NC/normal closed switch type)
3
Up (CW) control button input
(NO/normal open switch type)
CCW(Down) hard-limit switch input
(NC/normal closed switch type)
4
+5VDC output (optional)
+5VDC output (optional)
Note: All inputs are internally pulled-up to +5V, and then activated by a short (externally switch) to the
GND pin.