background image

Fieldbus Dependent I/O Module

INTERBUS

Manual

Technical Description,
Installation and
Configuration

752-122/000-002
Version 1.0.0

Содержание WAGO-I/O-SYSTEM 752

Страница 1: ...Fieldbus Dependent I O Module INTERBUS Manual Technical Description Installation and Configuration 752 122 000 002 Version 1 0 0...

Страница 2: ...49 0 571 8 87 5 55 Fax 49 0 571 8 87 4 30 E mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can neve...

Страница 3: ...g the Base Module 11 4 1 2 Insertion Extraction of the Electronic Module 12 4 1 3 Marking Label 12 4 2 Electrical Installation 13 4 2 1 General 13 4 2 2 Connection of the Module Supply Voltage 14 4 2...

Страница 4: ...2 Description 25 7 2 Module Properties 26 7 3 Process Image and Diagnostic Status Bits 27 7 3 1 Process Image 27 7 3 2 Diagnostic Status Bits 27 7 4 Fieldbus Controller Boards 28 7 5 Configuration So...

Страница 5: ...ed to without reference to patent rights For this reason the existence of such rights cannot be excluded 1 1 2 Personnel Qualification The use of the product described in this manual is solely intende...

Страница 6: ...3 Symbols Warning Observe this information in all cases to protect the system from damage Attention Marginal conditions to be observed in all cases to ensure a troublefree opera tion ESD Electrostati...

Страница 7: ...iations BA Bus Active DI 1 Digital input 2 Data In interface pin designation DO 1 Digital output 2 Data Out interface pin designation DS Diagnostic status I O Input Output ID Identifier Identification...

Страница 8: ...input interface Fieldbus connection output interface Power supply terminal blocks for internal electronics and external sensors Sensor signal DI Sensor supply Release clip 0V Actuator signal DO Actua...

Страница 9: ...O 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 0V 24V Fig 2 2 Base Module g1x2406x Fieldbus connection 2 x 9 pole D SUB Module power supply terminal block wi...

Страница 10: ...se module If a replacement of the electronic module is necessary the wiring remains undisturbed Status indicators for fast diagnostics The electronic module includes a marking label for input output i...

Страница 11: ...code 0x03 amount of data 32 bit Supply Supply voltage DC 24 V 15 20 Current input module without load 100 mA for 24 V DC Total loss of power 4 5 W Fuse F1 for sensor supply TR5 250 V 6 3A T General in...

Страница 12: ...t circuit protection electronic automatic restart Max operating frequency without bus resistive load inductive load 1 kHz utilization category DC 13 equals 6 Hz Insulation electronics field side none...

Страница 13: ...pection Fc 10 57 Hz constant amplitude 0 075 mm 57 150 Hz constant acceleration 1 g Impact According to IEC 60068 2 27 15 g 11 ms Electrical Safety Reverse voltage protection Yes Air and creepage dist...

Страница 14: ...ITEM NO 752 824 INPUT I OUTPUT O 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 0V 24V INTERBUS READY BA OVERLOAD PUSH PUSH WAGO I O SYSTEM 752 16DI 16DO 752 3...

Страница 15: ...tool screw driver as shown in Fig 4 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 17 18 25 26 WAGO I O SYSTE...

Страница 16: ...ugging in the electronic module g1x2402x The electronic module is correctly inserted when all four latches have en gaged INTERBUS READY BA OVERLOAD PUSH PUSH WAGO I O SYSTEM 752 16DI 16DO 752 324 RC R...

Страница 17: ...a plug All connecting terminal blocks for the supply voltages and sensor and actuator connections are equipped with CAGE CLAMP connectors These CAGE CLAMP connectors are suitable for fine stranded an...

Страница 18: ...base module to ensure electrical contact between the grounded carrier rail and the I O module The contacts are directly connected to the terminal block Note Ensure that solid contact is made between t...

Страница 19: ...of the field devices Vertical connection group for one channel Fig 4 7 Sensor connection g1xxx03e 2 conductor sensors e g switches are connected to the grey and red terminal blocks 3 conductor sensor...

Страница 20: ...hipped with jumpers installed in each of these termi nals connecting 24VDC module power to connection point for the output supply voltage 24 V 0 V 1 2 3 33 34 35 4 5 6 7 8 17 18 36 37 38 39 40 Outputs...

Страница 21: ...al blocks This row of terminal blocks will be wired back to the source common of the supply poten tial 4 2 5 Connection of the Output Signals The output signal terminals are identified by the imprint...

Страница 22: ...ly isolated between the fieldbus and the module 1 6 7 8 9 2 3 4 5 5 V RBST GND DI2 DI2 DO2 DO2 Output interface 9 pole D Sub female Fig 4 14 Socket connection assignment g1xx403e Note A jumper in the...

Страница 23: ...DO DO DO DO DI DI GND DO DO DI DI 9 pole D SUB female Color coding Yellow Green Grey Pink Brown 9 pole D SUB male Jumper Cable grip Cable grip Fig 4 15 Example of a remote bus cable g1xx401e i Further...

Страница 24: ...resentation of the input output and supply circuitry are shown in Fig 5 1 100nF 100nF 100nF 100nF 100nF 10nF 0 V 24 V 6 3 A DI DO DI 1 16 DO 1 16 Input interface Output interface Supply of the output...

Страница 25: ...3 4 5 6 7 8 OUTPUT 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 3 1 2 Fig 6 1 Status Indicators g1x2405x 1 Fieldbus INTERBUS specific status indicators 2 Interference...

Страница 26: ...tors LED Color Status Meaning READY Operational Green ON OFF The supply voltage is in the permissible toler ance range the equipment is operative Equipment not operative insufficient supply voltage BA...

Страница 27: ...ge to the output drivers Fault of an output driver Feedback A fault is detected if a transmitted value of 1 by the master controller does not produce a threshold voltage at a corresponding output When...

Страница 28: ...o fieldbus vari ants of which should be mentioned for the decentralized periphery Remote bus Installation remote bus 7 1 1 Features of the Remote Bus 1 master max 512 slaves Ring structure with active...

Страница 29: ...Remote bus device Remote bus device Remote bus device Remote bus device Remote bus device Bus coupler Fig 7 1 INTERBUS remote bus topology g112200e Possible configuration Fieldbus master WAGO I O SYST...

Страница 30: ...h slave has an ID register identification register containing information about the type of module the number of I O addresses and status and fault conditions INTERBUS recognizes two operating modes 1...

Страница 31: ...Word of the I O module in the input process image Word 0 out 1 Word of the I O module in the output process image Word 1 out 2 Word of the I O module in the output process image x Bit position in the...

Страница 32: ...s the LED off again once the fault has been corrected and after a 1 second delay cancels the periphery fault message 7 4 Fieldbus Controller Boards Master control systems such as PLC s communicate to...

Страница 33: ...n I O module using WAGO NETCON 1 Start WAGO NETCON Fig 7 2 WAGO NETCON icon p932x00x 2 Create a new project Create a new project and select INTERBUS as the fieldbus system Menu path File New Fig 7 3 S...

Страница 34: ...as a slave Menu path Insert remote bus equipment Fig 7 5 Insert remote bus device p932x07e The devices on the INTERBUS network can be detected automatically by per forming an Automatic Network Scan Us...

Страница 35: ...driver the data is downloaded Fig 7 7 Download p932x04e 6 System Diagnostic Tools within WAGO NETCON All input and output signals can be easily monitored and or set using the inte grated I O monitor...

Страница 36: ...further description of this software 1 Start CMD Fig 7 10 CMD icon p932x08x 2 Create a new project Create a new project for your application Menu path File New Fig 7 11 CMD main window p932x09e 3 Sel...

Страница 37: ...n the controller board icon and select the menu item Insert with ident code to manually insert a device into the network configuration Fig 7 13 Insert remote bus device p932x16e Once inserted further...

Страница 38: ...16 DI 16DO 752 102 1 sheet 9 labels Replacement fuse F1 TR 5 250 V 6 3A T Micro fuse according to IEC 127 3 Note Use UL Recognized fuse only 752 180 5 Felt tipped pen for non smudge writing 210 110 1...

Страница 39: ...ich co ordinates the bus traffic and transfers the data to a control system Group Input output group connection group General grouping of I O channels With their 8 chan nels outputs form a supply grou...

Страница 40: ...WAGO Kontakttechnik GmbH P O Box 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Telephone 05 71 8 87 0 Telefax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...