60 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 48.5 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Nor men und Richtlini en/EM V-Nor men F Bkoppl er/-contr oller 750- xxxx/0040- 0000, ohne Vari antenangabe - Einlei tung XTR @ 18\mod_1395916932582_21.docx @ 149711 @ @ 1
The fieldbus coupler/controller 750-352/040-000 meets the following EMC
standards as these standards relate to the fieldbus coupler/controller:
Pos: 48.6 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Nor men und Richtlini en/Nor men Störfestig keit XTR (Bundl e 1-3) @ 18\mod_1394030613258_21.docx @ 147348 @ @ 1
Table 25: EMC – Immunity to Interference
Standard
Test Value
Electrostatic Discharge
• EN 61000-4-2
• EN 60255-26
• IEEE C37.90.3
8 kV (contact discharge)
8 kV (air discharge)
High-frequency Electromagnetic Fields
• EN 61000-4-3
• EN 60255-26
• IEEE C37.90.2
20 V/m (80 MHz … 1 GHz)
10 V/m (1 GHz … 3 GHz)
Fast Electrical Transient Disturbances / Burst
• EN 61000-4-4
• EN 60255-26
• IEEE C37.90.1
4 kV
Surge Voltage / Surge
• EN 61000-4-5
• EN 60255-26
1 kV (conductor/conductor)
2 kV (conductor/ground)
Conducted Disturbances, Induced by High-frequency Fields
• EN 61000-4-6
• EN 60255-26
10 V (150 kHz … 80 MHz)
Magnetic Fields With Electrical Frequencies
• EN 61000-4-8
• EN 60255-26
300 A/m continuous / 1000 A/m for 1 s
Pulse-shaped Magnetic Fields
• EN 61000-4-9
300 A/m
Damped Oscillatory Magnetic Fields
• EN 61000-4-10
100 A/m
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000-4-11
• EN 60255-26
Standard not applicable
Damped Sinusoidal Oscillations
• EN 61000-4-12
1 kV (conductor/conductor)
2 kV (conductor/ground)
Harmonics and Interharmonics
• EN 61000-4-13
Standard not applicable
Conducted Asymmetric Disturbances
• EN 61000-4-16
30 V continuous
300 V for 1 s