214 Fieldbus Communication
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
11.3.5.17 Discrete Output Point (66
hex
)
This class enables data exchange for a particular digital output point.
Instance 0 (Class Attributes)
Table 213: Discrete Output Point (66 hex) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1 ... 255 (Digital output value 1 up to 255)
Table 214: Discrete Output Point (66
hex
) – Instance 1...255
Attribute ID Access Name
Data type Description
Default
value
1
Get
DopObj_Value BYTE
Digital Output
(only Bit 0 valid)
-
Common Services
Table 215: Discrete Output Point (66
hex
) – Common service
Service
code
Service available
Service-Name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
11.3.5.18 Discrete Output Point Extended 1 (6A
hex
)
The extension of the “Discrete Output Point” class enables the exchange of data
from a fieldbus node that contains over 255 digital output points (DOPs). The
instance scope of the “Discrete Output Point Extended 1” class covers DOPs
from 256 to 510 in the fieldbus node.
Instance 0 (Class Attributes)
Table 216: Discrete Output Point Extended 1 (6A
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-