Table 140: Register Address 0x2031
Register address 0x2031 (8241
dec
) with a word count of up to 65
Value
Description of the connected I/O modules
Access
Read modules 65...128
Description
Length 1…64 words
The node configuration can be specified in the 0x2031 register. The item number
of the I/O modules or fieldbus coupler/controller (without leading 750) is listed in
order. Because order numbers cannot be read out of digital modules, a code is
displayed for them, as defined below:
Bit position 0
Input module
Bit position 1
Output module
Bit position 2…7
Not used
Bit position 8…14
Module size in bits
Bit position 15
Designation digital module
Table 141: Register Address 0x2032
Register address 0x2032 (8242
dec
) with a word count of up to 65
Value
Description of the connected I/O modules
Access
Read modules 129...192
Description
Length 1…64 words
The node configuration can be specified in the 0x2032 register. The item number
of the I/O modules or fieldbus coupler/controller (without leading 750) is listed in
order. Because order numbers cannot be read out of digital modules, a code is
displayed for them, as defined below:
Bit position 0
Input module
Bit position 1
Output module
Bit position 2…7
Not used
Bit position 8…14
Module size in bits
Bit position 15
Designation digital module
Table 142: Register Address 0x2033
Register address 0x2033 (8243
dec
) with a word count of up to 65
Value
Description of the connected I/O modules
Access
Read modules 193 ... 255
Description
Length 1…63 words
The node configuration can be specified in the 0x2033 register. The item number
of the I/O modules or fieldbus coupler/controller (without leading 750) is listed in
order. Because order numbers cannot be read out of digital modules, a code is
displayed for them, as defined below:
Bit position 0
Input module
Bit position 1
Output module
Bit position 2…7
Not used
Bit position 8…14
Module size in bits
Bit position 15
Designation digital module
Pos: 94.49 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/Z ugriff auf R egister werte - Konfigurationsregister 0x2040 @ 4\mod_1235636434734_21.docx @ 27821 @ @ 1
Table 143: Register Address 0x2040
Register address 0x2040 (8256
dec
)
Value
Implement a software reset
Access
Write (Write sequence 0xAA55 or 0x55AA)
Description
The fieldbus coupler/controller performs a restart by writing the values 0xAA55 or
0x55AA.
Pos: 94.50 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/Z ugriff auf R egister werte - Konfigurationsregister 0x2041, 0x2042, 0x2043 @ 8\mod_1278930636091_21.docx @ 59643 @ @ 1