WAGO-I/O-SYSTEM 750
Installing and Removing the I/O-IPC
43
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Pos: 36.1 /Serie 758 (Funk, IPC und PFC)/Montieren/Montage 758-87x Einleitung 1 @ 10\mod_1312436538898_21.doc @ 75830 @ 12 @ 1
6
Installing and Removing the I/O-IPC
The I/O-IPC has an elevated generation of heat. Excess heat is drawn off by
passive heat dissipation (aluminum underside of the I/O-IPC and mounting rail).
For this reason, the I/O-IPC shall always be mounted on a mounting rail.
6.1
Instructions for Installation/Removal
The following information shall always be observed:
Pos: 36.2 /Serie 758 (Funk, IPC und PFC)/Montieren/Montage 758-87x Sicherheitshinweis Achtung: Belüftung des Einbauorts 55° @ 10\mod_1313494510284_21.doc @ 77072 @ @ 1
NOTICE
Ventilation of the installation site
When installing the I/O-IPC, leave a free space on the sides and above of 40 mm
to achieve sufficient heat dissipation. The surrounding temperature at the
installation site shall not 55 °C during operation.
Pos: 36.3 /Serie 758 (Funk, IPC und PFC)/Montieren/Montage 758-87x Sicherheitshinweis ESD: Offene Schnittstelle @ 10\mod_1313494519690_21.doc @ 77076 @ @ 1
NOTICE
Open interface!
Unneeded interfaces of the I/O-IPC shall be closed with the accompanying
protective caps to prevent possible damage caused by electrostatic discharge.
Pos: 36.4 /Serie 758 (Funk, IPC und PFC)/Montieren/Montage 758-87x Einleitungsende 3 @ 10\mod_1313488048409_21.doc @ 77064 @ 22 @ 1
•
Select a sufficiently stable mounting rail and use several mounting points
(every 20 cm), if applicable, to prevent the I/O-IPC from bending and
twisting the mounting rail.
•
When using mounting rails with a height of 7.5 mm, use flat riveting or
sunken screws. Otherwise, the I/O-IPC and the connected I/O modules
cannot be correctly mounted on the mounting rail.
•
Take care that the physical interfaces are not soiled during installation. This
can lead to damage and corrosion of the contacts.
•
To avoid damage to the I/O-IPC, do not install it within the shear ranges of
mobile systems or machine parts.
•
Arrange for an appropriate potential equalization in your system.
•
The mounting rails shall be screwed on so that they are grounded at the
installation site.