765-4501/0100-0000
Connection
78
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Table 50: Connecting an IO-Link Device or Digital Input or Output
Connection Option
Description
Connection of an IO-Link device
Required port configuration: IO-Link master and pin 2 disabled.
Connection of an IO-Link device and a digital input on channel B.
Required port configuration: IO-Link master and pin 2 as a digital input.
Connection of an IO-Link device and a digital output on channel B.
Required port configuration: IO-Link master and pin 2 as a digital output.
Connection of a digital input at channel A.
Required port configuration: pin 4 as digital input and pin 2 disabled.
Connection of two digital inputs on channels A and B.
Required port configuration: pin 4 and pin 2 as digital inputs.
Connection of a digital output on channel A.
Required port configuration: pin 4 as a digital output and pin 2 disabled.
Connection of two digital outputs on channels A and B.
Required port configuration: pin 4 and pin 2 as digital outputs.
Connection of a digital input on channel A and a digital output on channel B.
Required port configuration: pin 4 as a digital input and pin 2 as a digital out-
put.