765-4501/0100-0000
Properties
Product manual | Version: 1.1.0
23
8PORT IOL-A FLD EI DC 24V 2.0A
4.4.5 Electrical Safety
Table 12: Electrical Safety
Property
Value
Insulation resistance
60 VDC
Test voltage
550 VAC RMS
Min. creepage distance
0.7 mm
Requirements
• Use of PELV/SELV power supplies (limited to 60 VDC)
• When SELV power supplies are used: SELV power supplies with supply via the same
network phase
• If PELV (Protective Extra Low Voltage) power supplies are used: PELV (Protective Ex-
tra Low Voltage) power supplies with a secondary power supply connection to the
common reference point
4.4.6 Environmental Conditions
Table 13: Environmental Conditions
Property
Value
Surrounding air temperature (operation)
–25 °C ... +70 °C
Surrounding air temperature (storage)
–40 °C ... +80 °C
Maximum temperature change
3 K/min
Relative humidity (operation)
5 % ... 95 %
Pollution degree
3 (EN 60664-1)
Operating altitude
0 ... 2000 m
Overvoltage category
II (EN 60664-1)
Protection type
IP67 (EN 60529)
Protection class
III (EN 61140)
Vibration resistance
5g (IEC 60068-2-6)
Shock resistance
50g (IEC 60068-2-27)
4.4.7 Communication
Table 14: Communication
Property
Value
Communication Interfaces
ETHERNET, IO-Link, Bluetooth®
Protocols
EtherNet/IP, HTTP, OPC UA, IO-Link
Table 15: Communication – EtherNet/IP device
Property
Value
Connection 1 (Exclusive Owner – 32 bytes per IO-Link
port)
Input data: 276 bytes; output data: 276 bytes
Connection 2 (Exclusive Owner – 32 bytes per IO-Link
port without config)
Connection 3 (Listen only – 32 bytes per IO-Link port)
Input data: 276 bytes; output data: 0 bytes
Connection 4 (Input Only – 32 bytes per IO-Link port)
Connection 5 (Exclusive Owner – 16 bytes per IO-Link
port)
Input data: 148 bytes; output data: 148 bytes
Connection 6 (Exclusive Owner – 16 bytes per IO-Link
port without config)