2787-2147
Properties
20
Product manual | Version: 1.0.0
Power Supply Pro 2
Table 19: Technical Data – Output
Property
Value
Power Boost
30 A (5 s)
Top Boost
120 A (15 ms)
Derating of output power
See section
8
Line regulation
2)
< 0.02 %
Load regulation
3)
< 2.0 %
Residual ripple/noise
4)
< 70 mV
Overload behavior
5) 6)
“Constant Current” mode
1)
“Constant current with latching shutdown
“Hiccup” mode
“Electronic Circuit Breaker” mode
“Latching Shutdown on Thermal Overload” mode
“Power Boost” mode
“Top Boost” mode
Switch-on delay (typ.)
6) 7)
230 VAC
< 1.5 s
1)
Factory setting
2)
Nominal load, in range 90 ... 264 VAC
3)
10 % / 90 % load step
4)
20 MHz bandwidth
5)
See section
8
Short-Circuit and Overload Behavior [
6)
Can be set via the WAGO Interface Configuration software
7)
See figure “Turn-on Time”
Overshoot
Turn on Time
Input
Voltage
Output
Voltage
Figure 10: Turn-on Time
!
NOTICE
Select conductor cross-sections according to current load!
In the event of a fault, the output current of a power supply can be up to 1.5 × I
OUT
. Only
use conductor cross-sections sufficient for the current load!
Table 20: Technical Data – Output Connection
Property
Value
Cross-section
Solid
0.50 … 10 mm² / 20 … 8 AWG
Fine-stranded
0.50 … 10 mm² / 20 … 8 AWG
Insulated ferrule with plastic collar
0.50 … 6.0 mm²
Ferrule without plastic collar
0.50 … 6.0 mm²
Strip length
13 to 15 mm / 0.51 to 0.59 in