32 Commissioning
WAGO-PERSPECTO 762
762-2035, -2057, -2104, -2121, -2150 PERSPECTO VP, Visu-Panel
5.2
IP address of the device
5.2.1
General
The device can also be programmed using the WAGO-AUTOMATION
COCKPIT. A TCP/IP connection is required. An IP address must be assigned to
the device after switching it on for the first time.
The WAGO Control Center installed on the device is used to assign the IP address
by default (observe "Einstellen der IP-Adresse" section).
The device can either draw its IP address from a DHCP server on the network or
the device can be assigned a fixed IP address.
The current IP address can be queried by double-clicking on the network icon in
the system tray in the task bar.
Note
DHCP / fixed IP address
The device must be connected to a network to change the IP address from DHCP
to a fixed IP address.
Note
Subnet
To use the Auto-Scan function from the WAGO-AUTOMATION COCKPIT, the
devices must be set to the same subnet.
Note
Telnet Access
The HMI runtime (Runtime mode) must be running for programming and access
via Telnet.
Manual
Version 1.0.0