Fieldbus coupler/controller
• 91
Review
Modular I/O System
L
ON
W
ORKS
®
3.2.11 Technical Data
System data
No. of nodes
64 without repeater, 127 with repeater
Transmission medium
Twisted Pair - FTT
Max. length of fieldbus segment
free topology 500 m,bus topology 2700 m
Topology
in accordance with LON specification
Baud rate
78 kbps
Buscoupler connection
2-pole male connector, series 231 (MCS)
female connector (231-302) is included
Programmierung WAGO-I/O-PRO
32
IEC 61131-3
IL, LD, FBD, ST, FC
Standards and approvals
UL
E175199, UL 508
Conformity marking
CE
Accessories
Miniature WSB quick marking system
WAGO TOPLON CD
759-340/000-002
Configuration cable
750-920
(Connection Fieldbus Coupler/Controller <->
WAGO-I/O-PRO)
WAGO-I/O-PO 32 eng.
759-332/000-002
Technical data
Max. number of I/O modules
62 per node
digital signals
max. 248 (Inputs and Outputs)
analog signals
max. 124 (Inputs and Outputs)
Config. possibility
via PC with LON interface
Program memory
128 kByte
Data memory
64 kByte
Non-volatile memory
7 kByte (retain)
Voltage supply
DC 24 V (-15 % / + 20 %)
Input current
max
500 mA at 24 V
Efficiency of the power supply
87 %
Internal current consumption
300 mA at 5 V
Total current for I/O modules
1700 mA at 5 V
Isolation
500 V system/supply
Voltage via power jumper contacts
DC 24 V (-15 % / + 20 %)
Current via power jumper contact
max
DC 10 A
Transceiver
FTT 10 A