78 •
Fieldbus coupler/controller
Review
L
ON
W
ORKS
®
20 x bit %IX475.0-%IX476.3
20 x bit %QX475.0-%QX476.3
Tab. 3-5: Presetting addresses in the template file Template_750-819.pro
This template can be upgraded and modified at any time.
Once the IEC 61131 application programmed in WAGO-I/O-
PRO
32 has been
compiled, all declared variables can be stored in a Symbol-file (SYM-file).
After downloading the SYM-file in the WAGO
TOPLON
®
PRIO plug-in, all
variables are ready to be linked with network variables.
Note
Given that all variables are automatically imported from the template into the
standard WAGO
TOPLON
®
PRIO application, unused variables should not
be deleted from the template in order to achieve a better clarity.
3.2.6.2.3 Addressing the configuration variables
Variables used for external configuration via the LON fieldbus are absolute
addressed in double flag words. The address range begins with %MD1792 and
has a capacity of 128 variables.
After downloading the SYM-file into WAGO
TOPLON
®
PRIO, all defined
configuration variables are ready to be linked with CPs (Configuration Proper-
ties) just like the PFC variables.
3.2.7 Starting-up LON fieldbus nodes
The general procedure for starting up a WAGO LON fieldbus node with the
fieldbus controller 750-819 is described step-by-step for
TOPLON
®
PRIO in
the brief instructions WAGO
TOPLON
®
(Quickstart, Item no.: 759-123/000-
002 part 7).
These should form a guideline for further projects.
i
More information
The brief instructions WAGO
TOPLON
®
(Quickstart,
Item no.: 759-123/000-002 part 7) can be found in the Internet under:
http://www.wagotoplon.com/html/eng/service/manual/index.htm
Attention
This description is given as an example and is limited to the execution of a
local start-up of an individual LON fieldbus node with
TOPLON
®
PRIO.
3.2.8 Programming the PFC with WAGO-I/O-PRO 32
Due to the IEC 61131 programming of the LON fieldbus controller
750-819 you have the option to use the functionality of a PLC.