82 •
Fieldbus coupler/controller
Review
L
ON
W
ORKS
®
3.2.8.2 IEC 61131-3 Program transfer
Program transfer from the PC to the controller following programming of the
desired IEC 61131 application can be made in two different ways:
•
via the serial interface or
•
via the fieldbus.
3.2.8.2.1 Transmission via the serial interface
Use the WAGO communication cable to produce a physical connection via the
serial interface. This is contained in the scope of delivery of the programming
tool IEC 1131-3, order No.: 759-332/000-002, or can be purchased as an ac-
cessory under order No.: 750-920.
Connect the COMX port of your PC with the communication interface of your
controller via the WAGO communication cable.
Warning
The communication cable 750-920 must not be connected or disconnected
while the coupler/controller is powered on!
A communication driver is required for serial data transmission. In
WAGO-
I/O-PRO 32,
this driver and its parameters are entered in the
"Communica-
tion parameters"
dialog.
i
More information
Please find more information on the installation of the communication driver
and the detailed description of software handling in the manual
WAGO-I/O-PRO 32
(order no.: 759-122 / 000-001).
1. Start
the
WAGO-I/O-PRO 32
software via ’Start/Programs’ or by double
clicking on the WAGO-I/O-PRO-32 symbol on your desk top.
2. In
the
"Online"
menu click on the
"Communication parameters"
menu
point.
The dialog "Communication parameters" opens. The basic setting of this
dialog has not yet any entries.
3. In the selection window mark the desired driver on the right-hand dialog
side (i.e.
"Serial (RS232)"
, to configure the serial connection between PC
and the controller).
4. In the center window of the dialog, the following entries have to appear:
- Parity:
Even
- Stop bits:
1
If necessary, change the entries accordingly.
You can now commence testing the controller.