WAGO-I/O-SYSTEM 750
Device Description
21
753-501 2DO 24V DC 0,5A
Manual
Version 1.2.0
3.5.5
Connection
Table 12: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² ... 2.5 mm² / AWG 28 … 14
Stripped length
9 ... 10 mm / 0.37 in
Table 13: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning
Voltage drop at I
max.
< 1 V/64 modules
Table 14: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
3.5.6
Climatic Environmental Conditions
Table 15: Technical Data – Climatic Environmental Conditions
Operating temperature range
0 °C … 55 °C
Storage temperature range
−25 °C … +85 °C
Relative humidity without condensation Max. 95 %
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation