![WAGO I/O SYSTEM 750 750-671 Скачать руководство пользователя страница 191](http://html1.mh-extra.com/html/wago/i-o-system-750-750-671/i-o-system-750-750-671_manual_3328297191.webp)
Reference Commands for Move Mode
•
191
Math
commands
WAGO-I/O-SYSTEM 750
I/O Modules
3.2.4.2.7
VAR_COPY (0x56)
Copes one variable to another variable.
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
-
MB2
0x56
MB3
Target (1 … 8 corresponds to FILT1 … FILT8)
MB4
Source (1 … 8 corresponds to FILT1 … FILT8)
MB5 Reserved
Response
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
Return
Code
MB2
0x56
MB3 Reserved
MB4 Reserved
MB5 Reserved