![WAGO I/O SYSTEM 750 750-671 Скачать руководство пользователя страница 135](http://html1.mh-extra.com/html/wago/i-o-system-750-750-671/i-o-system-750-750-671_manual_3328297135.webp)
Reference Commands – Mailbox Commands
•
135
Table Management Commands
WAGO-I/O-SYSTEM 750
I/O Modules
3.1.4.4.2
TABLE_COPY (0x45)
Tables will be copied.
The target may not be identical to the source.
A table can not be specified either as the target nor as the source of the
copying command when transfer using DLD_START, DLD_CONT or
DLD_END has not been completed. Writing of the EEPROM is performed in
the background, independent of processing of the table command (see also
DIAG_QUERY_STORAGE).
The tables located in the EEPROM are always copied to RAM 1 when the
system is started up. This command can not be used for copying out of the
EEPROM.
A configuration table can not be copied with this command (see also
CFG_SAVE, CONFIG_RESTORE).
Copying options:
1. RAM
RAM
2. RAM
EERPOM