WAGO-I/O-SYSTEM 750
Connect Devices
65
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
6.3.3
Connection Examples for Digital Power Outputs
The PROFIsafe I/O module includes two semiconductor switches O1 and O2 that
can be used in four different output configurations to switch from loads up to 10
A rated current.
Digital power output O1 always switches in H-Side mode (High Side) to 24V
potential.
Digital power output O2 can either switch in H-Side mode (High Side) to 24V
potential or in L-Side mode (Low Side) to 0V potential depending on the output
configuration.
Table 24: Output configurations and response thresholds of the external voltage monitoring
H-Side/L-Side 1
H-Side/H-Side 1
H-Side/L-Side 2
H-Side/H-Side 2
Figure 26: H-Side/L-
Side 1
Figure 27: H-Side/H-
Side 1
Figure 28: H-Side/L-
Side 2
Figure 29: H-Side/H-
Side 2
Response thresholds of the external voltage monitoring
U
O1Bmin.
3.9V
U
O2Bmin.
1.39V
U
O1Bmin.
3.9V
U
O1Bmin.
3.9V
U
O1Bmax.
10.98V U
O2Bmax.
3.92V
U
O1Bmax.
10.98V U
O1Bmax.
10.98V
U
O2Amin.
1.28V
-
-
U
O2Amin.
1.28V
U
O2Bmin.
1.39V
U
O2Amax.
1.64V
-
-
U
O2Amax.
1.64V
U
O2Bmax.
3.92V
The
Output Configuration
parameter is used to configured the connection type
used (see
Output Configuration
parameters).