WAGO-I/O-SYSTEM 750
Connect Devices
51
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
6
Connect Devices
6.1
Connecting a Conductor to the CAGE CLAMP
®
The WAGO CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Only connect one conductor to each CAGE CLAMP
®
connection!
Only one conductor may be connected to each CAGE CLAMP
®
connection.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Exception:
If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule to
join the wires together. The following ferrules can be used:
Length
8 mm
Nominal cross section
max.
1 mm
2
for 2 conductors with 0.5 mm
2
each
WAGO Product
216-103 or products with comparable properties.
1.
To open the CAGE CLAMP
®
insert the actuating tool into the opening
above the connection.
2.
Insert the conductor into the corresponding connection opening.
3.
To close the CAGE CLAMP
®
simply remove the tool - the conductor is
then clamped firmly in place.
Figure 18: Connecting a conductor to a CAGE CLAMP
®