750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
The following table lists the safe response times in the event of failure that result
from the input filter time set.
Table 21: Safe response time of the digital inputs in the event of failure
Input
filter time
Standard operating mode
Rotary table
operating
mode
Single-
channel
analysis
Valence
evaluation
equivalent
Valence
evaluation
antivalent
0 ms
35 ms
35 ms
19 ms
35 ms
0.5 ms
36 ms
36 ms
20 ms
36 ms
1 ms
38 ms
38 ms
21 ms
38 ms
2 ms
42 ms
42 ms
24 ms
42 ms
3 ms
47 ms
47 ms
28 ms
47 ms
5 ms
59 ms
59 ms
36 ms
59 ms
10 ms
89 ms
89 ms
56 ms
89 ms
20 ms
150 ms
150 ms
96 ms
150 ms
50 ms
331 ms
331 ms
217 ms
331 ms
100 ms
633 ms
633 ms
419 ms
633 ms
200 ms
1237 ms
1237 ms
821 ms
1237 ms