34
Device Description
WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
4.6.4
Digital Inputs
Table 14: Technical data, digital inputs
Inputs
I1 … I4
4 inputs type 1 acc. EN 61131-2
Achievable safety classes
4 x Cat. 2/PL d acc. EN ISO 13849-1,
2 x Cat. 4/PL e acc EN ISO 13849-1,
4 x SIL3 acc. EN 62061,
4 x SIL3 acc. IEC 61508
Input filter time
Configurable between 0 ms and 200 ms
in steps
(See section "Parameterization, Input
Filter Time Parameter")
Signal voltage
0
DC –3 V ... +5V
1
+15V ... +30V
Input current
typ.
2.2mA
Response Times
See section "Response Times"
Input frequency
max.
50 Hz (depending on filter time)
Input pulse duration
min.
See section "Input Filter Time
Parameter"
4.6.5
Digital Clock Outputs
Table 15: Technical data, digital clock outputs
Clock outputs
T1, T2
2
Clock pulse duration
at input filter time
0 ms
5 ms
0.5 ms
5 ms
1 ms
5 ms
2 ms
5 ms
3 ms
5 ms
5 ms
7 ms
10 ms
12 ms
20 ms
22 ms
50 ms
50 ms
100 ms
102 ms
200 ms
202 ms
Output nominal
current
T1
250 mA
T2
250 mA
Output protection
Short circuit and overload
Cable length
max.
unshielded
200 m (at 120 nF / km)
shielded
200 m (at 120 nF / km)