158 Appendix
WAGO I/O System Compact
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
15.1.1.2.13 “Configuration of Network Services” Page
The settings for various services are shown on the “Configuration of Network
Services” page.
Close any ports and services that you do not need!
Unauthorized persons may gain access to your automation system through open
ports.
To reduce the risk of cyber attacks and thus increase cyber security, close all
ports and services not required by your application in the control components
(e.g., port 6626 for WAGO-I/O-
CHECK
, port 2455 for CODESYS V2 and port
11740 for CODESYS V3).
Only open ports and services during commissioning and/or configuration.
“FTP” Group
Table 88: WBM “Configuration of Network Services” Page – “FTP” Group
Parameters
Explanation
FTP
Enable/disable the FTP service.
This service is disabled by default.
Click the
[Submit]
button to apply a change. The change takes effect
immediately.
“FTPS” Group
Table 89: WBM “Configuration of Network Services” Page – “FTPS” Group
Parameters
Explanation
FTPS
Enable/disable the FTPS service.
This service is disabled by default.
Click the
[Submit]
button to apply a change. The change takes effect
immediately.
“HTTP” Group
Table 90: WBM “Configuration of Network Services” Page – “HTTP” Group
Parameters
Explanation
HTTP
Enable/disable the HTTP service.
This service is disabled by default.
Click the
[Submit]
button to apply a change. The change takes effect
immediately.