WAGO I/O System Compact
Appendix 125
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
“Network TCP/IP Details” Group
The network and interface properties of the product are displayed in this group.
Table 60: WBM “Device Status” Page – “Network TCP/IP Details” Group
Parameter
Meaning
DIP Switch Status
Status of the address selection switch;
this area only appears if an address selection switch
is available.
DIP Switch Mode
Address Selection Switch
Off (0)
IP address assignment via e.g., WBM
static
(1 … 254)
Static IP address assignment via
address selection switch
dhcp
(255)
Dynamic IP address assignment via
DHCP
DIP Switch Value
Set value of the address selection switch
Bridge <n>
Bridge currently configured;
the properties are displayed in a separate area for
each configured bridge.
MAC Address
MAC address used for product identification and
addressing
IP Source
Current reference type of the IP address
None
No IP allocation method is selected; this
occurs, for example, if a bridge was
added due to changes to the bridge
configuration.
Select a source in the
Configuration
tab
on the
Networking
>
TCP/IP
Configuration
page.
static IP Static IP address assignment
dhcp
Dynamic IP address assignment via
DHCP
bootp
Dynamic IP address assignment via
BootP (if BootP is supported)
external The IP address may be assigned by the
fieldbus application; this occurs e.g., if
the IP address is controlled by the
PROFINET application.
IP Address
Current product IP address
Subnet Mask
Current product subnet mask