20 Device Description
787-1668/0000-0080 Electronic Circuit Breaker
Manual
Version 1.1.0, valid from firmware 2.4.0
3.4.2
Rotary Switch
A rotary switch, which can be used to set the trip current for the individual
channel, is assigned to each channel. The following settings are possible:
•
1 A
•
2 A
•
4 A
•
6 A
•
10 A
•
RC
Figure 8: Rotary switch
“RC” (Remote Control) Setting:
The IO-Link interface can be used to set the trip current in this setting. This can
be done acyclically from a program or via corresponding control software with
installed device description file “IODD”.
Observe trip curve!
Observe the trip curve given in the Section "Function Description" when setting
the individual channels.