Use of the Interference-Free Module in Safety Applications
WAGO-SPEEDWAY 767
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
Pos: 58.6 /Serie 767 (WAGO-SPEED WAY)/Einsatz in sicherheitsg erichteten Anwendung en/767- xxxx_M aß nahmen und Aufl agen für die geschirmte Spannungsversorgung des Moduls_4 @ 11\mod_1317280498953_21.docx @ 80015 @ 2 @ 1
12.3 Measures and Conditions for Shielded Power
Supply of the Module
Shielded version of U
A
and 0 V_U
A
in connecting lead for unprotected
installation required!
To prevent a short circuit of power supply U
A
with an external voltage, wires U
A
and 0 V_U
A
must be shielded in the connecting lead according to EN 60204-1 or
EN ISO 13849-2. The shield must have an overlap of at least 85 % and be reliably
connected to the connector.
Attach ground shield or use insulation monitoring!
The connecting lead ground shield and functional grounding connection of the
interference-free modules must be connected to lines 0 V_U
LS
and 0 V_U
A
. In
addition, insulation monitoring according to EN 61557 can also be used. See the
following illustrations:
Figure 23: Connection diagram for the common power supply
Figure 24: Connection diagram for the common power supply with insulation monitoring
Figure 25: Connection diagram for the isolated power supply
Pos: 58.7 /Dokumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Safety switch module
Safety switch module
Safety switch module
767-xxxx
767-xxxx
767-xxxx
Insulation
monitor
Fuse
Fuse
Fuse