50
Connecting Data and Supply Cables
WAGO-SPEEDWAY 767
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
Pos: 23.22 /Serie 767 ( WAGO-SPEED WAY)/Anschluss D aten- und Versorgungskabel/I/O-M odule/Anschluss_Sensoren/Aktoren 767- 58xx_8xM 8_2 Z ähler @ 7\mod_1268056131666_21.docx @ 51987 @ 2 @ 1
5.5
Connect Sensor/Actuator Cable
The sensor/actuator cable provides power to the connected sensors and actuators.
When using cables that have not been pre-assembled, make sure that these cables
are equipped with M8 plugs rated to IP67. The following table outlines the
assignment of the sensor/actuator connections:
Table 25: Digital inputs/outputs: connection assignment
Connection
Connection diagramm
IN/OUT
IN/OUT
X1, X3, X5, X7
X2, X4, X6, X8
Table 26: Counter: Assignment of channels for connection assignment
Channel
Connection
Counter
1
X1
1
2
X2
3
X3
4
X4
5
X5
2
6
X6
7
X7
8
X8
Pos: 23.23 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sicherheitshinweise/Achtung/Achtung: Höchste Strombel astbar bei t der Vers.kontakte( Sens.+ Akt.) und Sensor-/Achtung: Höchste Str ombelastbar beit der Vers.kontakte(Sens.+ Akt.) und Sensor-/Aktorstromaufn. 800 mA @ 16\mod_1373020034040_21.docx @ 125640 @ @ 1
The highest current carrying capacity of the supply contacts is 4 A!
Consider that the sensors and actuators are supplied with power from the U
A
supply line. Take into account when determining the current energy needs of the
U
A
supply line, the sensor and actuator power consumption.
The total maximum power consumption of the sensors/actors must not
exceed 800 mA!
Please note that the combined power consumption of all connected sensors/actors
is not to exceed 800 mA. The distribution of power among the existing
connections is depending on the individual power requirements of the
sensors/actors.