WAGO-SPEEDWAY 767
Device Description
27
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
3.7.7
Information on actuator selection
Table 14: Technical data – Information on actuator selection
Delay time hardware
from 0 to 1 (0 – 90 %)
from 1 to 0 (0 – 90 %)
90 µs (resistive load)
310 µs (resistive load)
Rise time
from 0 to 1
Fall time
from 1 to 0
Typically 60 µs (resistive load)
Typically 45 µs (resistive load)
Cable length, unshielded
≤ 30 m
Resistance to recovery
≤ 0.5 A (error: 1 channel)
Type of load
Inductive, resistive loads and lamps
Switching frequency
Inductive load, approx. 20 Hz
Resistive load, approx. 500 Hz
Lamp load, approx. 500 Hz
Recommended minimum load
50 mA
*
Parallel connection of 2 outputs
For power boost
for redundant actuation of a load
Type of protective circuit
External protection (e.g., recovery diodes)
Output resistance
< 0.4 Ω
*
Wrong diagnostics may occur at high switching frequencies with reduced load.
3.7.8
Operating state influence on output
Table 15: Technical data – Operating state influence on output
PLC CPU stop
Acc. to substitute value strategy
Interruption of field bus
Acc. to substitute value strategy
Interruption of S-BUS
0 V status
Supply voltage under rated voltage
tolerance
0 V status
Interruption of supply voltage
0 V status
Output operation
Non-latching
Overload behavior
Automatic restart
3.7.9
Counter 1 and 2 (configurable)
Table 16: Technical data – Counter 1 and 2 (configurable)
Event counter/Gate time measurement
/
pulse duration counter
Number (configurable)
2
Waveform
Rectangular pulses
Counting depth
16 bits
Counting/switching frequency
0 Hz … 1 kHz
(depending on the S-BUS cycle)