765-4102/0100-0000
Planning
Product manual | Version: 2.1.0
41
8PORT IOL-B FLD PN DC 24V 2.0A
Figure 6: Power Supply Group with 765-4102/0100-0000 – Connection Example 2
To do so, we consider port X01 of the 765-4102/0100-0000 module:
This has a load of 5.2 A = 2 A + 2 A + 0.5 A + 0.5 A + 0.2 A on pin 1. That exceeds the
maximum load capacity of 4 A and is thus not permissible. If the currents on X01 and X02
of the 765-1701/0200-0000 IO-Link Hub were increased, the overload protection would
constantly activate and could threaten destruction of the 765-4102/0100-0000 IO-Link
Master on its port X01.
6.3 Settings Options
6.3.1 PROFINET Parameters
“IO-Link Master” Parameters
The following table describes the parameters of the IO-Link master, including the sub-
modules for the IO-Link ports.
Table 32: “IO-Link Master” Parameters
Parameter Group
Parameters
Default
Value Range
Description
Digital IO layout con-
figuration
PD layout
0
0: port-based
Order of the process
data of the digital in-
puts and digital out-
puts:
bit 0 = port 1 pin 4,
bit 1 = port 1 pin 2,
bit 2 = port 2 pin 4,
bit 3 = port 2 pin 2, ...
1: pin-based
The order of the
process data of the
digital inputs and dig-
ital outputs:
bit 0 = port 1 pin 4,
bit 1 = port 2 pin 4,
bit 2 = port 3 pin 4,
bit 3 = port 4 pin 4,
...
bit 8 = port 1 pin 2,
bit 9 = port 1 pin 2, ...