765-1503/100-000
Commissioning
64
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
Table 38: “Port Mode” Drop-Down Menu: Selecting the Operating Mode for Pin 2 and Pin 4 of the Selected IO-
Link Port
Selection Option
Description
Digital Output
The port is used as a digital output. All elements of the port configuration are ig-
nored except for the input and output data length.
Digital output, static on
The port is used as a digital output. The signal on pin 2 or pin 4 is permanently set
to logic 1.
Setting the Filter Time for Digital Inputs
The filter time for the digital inputs can be selected from the
Digital input signal filter
drop-down menu. You can select from the following values:
• No digital input filter
• 3 ms
• 15 ms
• 20 ms
If the
No digital input filter
option is selected, no filtering occurs.
10.3.1.4.2 Configuring IP Parameters
Figure 16: Settings
Menu Item
, Device Configuration
Tab
(Example View)
The
Device configuration
tab allows you to do the following:
• Specify how the module gets its IP address (via the
Configuration control
drop-down
menu with the STATIC, BOOTP und DHCP options)
Table 39:
Configuration Control
Drop-Down Menu
#
Option
Description
0
STATIC
The module’s IP address is configured statically. This is done using the module IP ad-
dress, the subnet mask and the gateway IP address entered on the “Device configura-
tion” tab.
1
BOOTP
The module gets its IP address with the BOOTP protocol.
2
DHCP
The module gets its IP address with the DHCP protocol. This is the standard setting.