765-1205/100-000
Commissioning
Product manual | Version: 2.0.0
65
8DIO FLD EC DC 24V 2.0A
Table 39: “Port Mode” Drop-Down Menu: Selecting the Operating Mode for Pin 4 of the Selected IO-Link Port
Selection Option
Description
Digital input, normally
open
The port is used as a digital input. All elements of the port configuration are ig-
nored except for the input and output data length.
Digital input, normally
closed
The port is used as a digital input. The signals to the port are inverted. All elements
of the port configuration are ignored except for the input and output data length.
Digital Output
The port is used as a digital output. All elements of the port configuration are ig-
nored except for the input and output data length.
Digital output, static on
The port is used as a digital output. The signal on pin 4 is permanently set to
logic 1.
Setting the Filter Time for Digital Inputs
The filter time for the digital inputs can be selected from the
Digital input signal filter
drop-down menu. You can select from the following values:
• No digital input filter
• 3 ms
• 15 ms
• 20 ms
If the
No digital input filter
option is selected, no filtering occurs.
10.3.1.4.2 Configuring IP Parameters
Figure 17: Settings
Menu Item
, Device Configuration
Tab
(Example View)
The EtherCAT
®
master configures the module’s IP address. Therefore, with EtherCAT
®
modules, no manual IP address configuration is necessary.
Other tabs under the menu item
Settings
are described below.