765-1103/100-000
Commissioning
Product manual | Version: 2.2.0
91
16DO FLD PN DC 24V 2.0A
Figure 36: GetForcingID Method: Unsuccessful
4. In the OPC UA client, drag the “AssignedForceID” node into the
Data Access View
window so that the AssignedForceID is read regularly
ð
Regular reading of the AssignedForceID triggers the watchdog timer and keeps
the Force function enabled.
10.3.3.1.10.4 Forcing Digital Outputs
The OutputPin2 method sets the output value of pin 2 of one or more ports. The Output-
Pin4 method sets the output value of pin 4 of one or more ports.
Requirements
• You must have an OPC UA client.
• You must know the username and password, and this user must have permission to
execute methods.
• You must have already established a connection to the I/O module.
• The Force function must be enabled, i.e. you must know the Force ID.
• The pin must be configured as a digital output.
Step-by-Step Instructions
1. In the
Address Space
window, open the context menu:
Root > Objects > De-
viceSet > [device name] > Forcing > OutputPin4
2. In the context menu, select
Call
.
ð
The
Call OutputPin4 on Forcing
window appears.
3. Enter the
Force ID
, the
Force Mask
and the
Force Data
(the input arguments are
described below, including an example).