765-1103/100-000
Planning
Product manual | Version: 2.2.0
41
16DO FLD PN DC 24V 2.0A
Parameter
Group
Parameter
Default
Value
Value
Range
Description
Bluetooth
timeout con-
figuration [s]
30
5 ... 60
Switch-off time of the Bluetooth
®
interface if not used;
A new Bluetooth
®
connection can be established by an
optical signal after the Bluetooth
®
interface is reactivated.
The unit for the switch-off time is seconds. The default
value is 30 seconds. Entering 0 is not allowed, since the
Bluetooth
®
interface must always switch off after the
switch-off time elapses.
PIN 4 digital
output con-
figuration
Port 1, port
, ..., port 8
2
2: digital
output
Pin 4 is a digital output.
3: PIN de-
activated
Pin 4 is deactivated.
PIN 2 digital
output con-
figuration
Port 1,
port 2, ...,
port 8
2
2: digital
output
Pin 2 is a digital output.
3: PIN de-
activated
Pin 2 is deactivated.
6.3.2 Setting the PROFINET Configuration
The PROFINET device has a modular structure. Slot 0 is the PROFINET access point
with four submodules. Slot 1 contains the digital output module for the process data.
Table 29: PROFINET Modules and Submodules
Slot
Subslot
Submodule
Description
0
1
DAP
Device access point (fixed)
0
32768
PN-IO
PROFINET interface
(fixed)
0
32769
Port 1
Port 1 (fixed)
0
32770
Port 2
Port 2 (fixed)
1
1
16 Digital Output Module
16 digital outputs (fixed)
2 input bytes and 2 output
bytes