WAGO-I/O-SYSTEM 758
Configuration
33
758-915
Bluetooth
®
ETHERNET Gateway
Manual
Version 1.1.0, applicable from FW/HW Version 01/01
Enable de-activated WBM using the Mode membrane button!
If autoconfiguration is conducted with PROFINET optimization, the device de-
activates the Web-based Management System to provide short cycle times.
Consequently, configuration can only be changed using the Mode membrane
button. Reset the device to the factory default settings to enable access to the
Web-based Management System again.
7.2.2
Selection and Activation of an Autoconfiguration
Procedure
General procedure:
1.
Switch off the power supply to the WEG and then re-activate power supply
to the device.
The Power LED lights up.
2.
Within
the first 5 seconds
after applying power, press the Mode membrane
button to switch to the operating mode “Configuration selection”.
LED A lights up and the operating mode “Configuration selection” is active.
If this is not the case, repeat steps 1 and 2.
3.
Select the autoconfiguration procedure:
Select the required autoconfiguration procedure by pressing the Mode
membrane button until the appropriate combination of LEDs lights up (see
previous section “Overview of Autoconfiguration Procedures”).
If you have switched through all the operating modes in order, you can
return to the first option in the order by pressing the button again.
Configuration is halted if the Mode membrane button is not pressed for 20 s!
The mode “Configuration selection” is de-activated automatically if you do not
press the Mode membrane button for selecting the autoconfiguration procedure.
The WEG will then start up using the previous settings.
4.
Activate autoconfiguration procedure:
To execute the selected autoconfiguration procedure press the Mode
membrane button again and hold it in for
at least 2 seconds
until the LED