40 Process Image
753-1630 SMI Master Module 230 V AC
Manual
Version 1.2.0 FW/HW Version 02/01
Pos: 77 /Serie 753 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/FT&K/Prozessabbild 753-1630, -1631/Prozessabbild 753-1630, -1631 - Control-/Statusbyte @ 28\mod_1478705543803_21.docx @ 386878 @ 2 @ 1
5.1
Control/Status Byte
The control/status byte is shown in the process image independent of user-
specific parameterization of the SMI master module.
If bit 7 is set in the control byte, register communication is always active and
process data communication inactive.
Table 16: Control Byte C0
Control byte C0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RegCom
--
Mailbox
-
-
-
-
-
-
Not used
--
Reserved
Mailbox
Mailbox 2.0 in the process data
0 – Mailbox deactivated
1 – Mailbox activated
RegCom
Register communication
0 – Register communication deactivated
1 – Register communication activated
In the status byte, only another diagnostic is shown next to the diagnostic of a
general error in the event of an error. If several errors are detected at the same
time, the diagnostic with the highest priority is shown (see table below).
Table 17: Status byte S0
Status Byte S0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RegCom
General
Error
Mailbox
Short
circuit
Field
supply
-
-
-
-
Not used
Field-side
supply
Undervoltage field supply
0 – Power supply is sufficient.
1 – Power supply is too low
Medium priority
Short circuit
SMI short circuit detection:
0 – No short circuit detected
1 – Short circuit on the SMI connections detected
Low priority
Mailbox
Mailbox 2.0 in the process data:
0 – inactive
1 – active
General Error General error status with inactive register
communication:
0 – inactive
1 – active
High priority
RegCom
Register communication:
0 – inactive
1 – active