13.3.5.11 DALI/DSI Master Module
750-641
The DALI/DSI Master module has a total of 6 bytes of user data in both the Input
and Output Process Image (5 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 3
words mapped into each image. Word alignment is applied.
Table 403: DALI/DSI Master module 750-641
Input Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
D0 S
DALI
Response
Status
byte
D2
D1
Message 3
DALI Address
n
D4
D3
Message 1
Message 2
The specialty modules represent 1x6 bytes input data and seize 1
Instance in Class (0x67).
Output Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
D0 C
DALI command,
DSI dimming value
Control byte
D2 D1
Parameter
2
DALI
Address
n
D4
D3
Command extension
Parameter 1
And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
13.3.5.12 EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 2
words mapped into each image. Word alignment is applied.
Table 404: EnOcean Radio Receiver 750-642
Input Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
n D0
S Data
byte
Status
byte
n+1 D2
D1
Data
bytes
Output Process Image
Byte Destination
Instance
High Byte
Low Byte
Description
n
-
C
not used
Control byte
n+1 -
-
not
used
The specialty modules represent 2x2 bytes input and output data and seize 2