![WAGO 750-880 Скачать руководство пользователя страница 345](http://html2.mh-extra.com/html/wago/750-880/750-880_manual_3156225345.webp)
WAGO-I/O-SYSTEM 750
I/O Modules 345
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Table 375: 2 Channel Digital Input Modules with Diagnostics and Input Process Data 75x-506
Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnostic
bit S 3
Channel 2
Diagnostic
bit S 2
Channel 2
Diagnostic
bit S 1
Channel 1
Diagnostic
bit S 0
Channel 1
Diagnostic bits S1/S0, S3/S2: = ‘00’
standard mode
Diagnostic bits S1/S0, S3/S2: = ‘01’
no connected load/short circuit a24 V
Diagnostic bits S1/S0, S3/S2: = ‘10’
Short circuit to ground/overload
The output modules seize 4 Instances in Class (0x65).
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
not
used
not
used
controls
DO 2
Channel 2
controls
DO 1
Channel 1
And the output modules seize 4 Instances in Class (0x66).
13.3.2.4 4 Channel Digital Output Modules
750-504, -516, -519, -531,
753-504, -516, -531, -540
Table 376: 4 Channel Digital Output Modules
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
controls
DO 4
Channel 4
controls
DO 3
Channel 3
controls
DO 2
Channel 2
controls
DO 1
Channel 1
The output modules seize 4 Instances in Class (0x66).
13.3.2.5 4 Channel Digital Output Modules with Diagnostics and Input
Process Data
750-532
The digital output modules have a diagnostic bit for each output channel. When an
output fault condition occurs (i.e., overload, short circuit, or broken wire), a
diagnostic bit is set. The diagnostic data is mapped into the Input Process Image,
while the output control bits are in the Output Process Image.
Table 377: 4 Channel Digital Output Modules with Diagnostics and Input Process Data
Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnostic
bit
S 4
Channel 4
Diagnostic
bit
S 3
Channel 3
Diagnostic
bit
S 2
Channel 2
Diagnostic
bit
S 1
Channel 1
Diagnostic bit S = ‘0’
no Error
Diagnostic bit S = ‘1’
overload, short circuit, or broken wire