![WAGO 750-880 Скачать руководство пользователя страница 249](http://html2.mh-extra.com/html/wago/750-880/750-880_manual_3156225249.webp)
WAGO-I/O-SYSTEM 750
Fieldbus Communication 249
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 109.39 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/Zugriff auf Registerwerte - Konfigurationsregister 0x1022 bis 0x1025 @ 3\mod_1235461775390_21.doc @ 27632 @ 4 @ 1
12.2.5.4 Configuration Registers
The following registers contain configuration information of the connected
modules:
Table 147: Register address 0x1022
Register address 0x1022 (4130
dec
)
Value
CnfLen.AnalogOut
Access
Read
Description
Number of word-based outputs registers in the process image in bits (divide by
16 to get the total number of analog words)
Table 148: Register address 0x1023
Register address 0x1023 (4131
dec
)
Value
CnfLen.AnalogInp
Access
Read
Description
Number of word-based inputs registers in the process image in bits (divide by 16
to get the total number of analog words)
Table 149: Register address 0x1024
Register address 0x1024 (4132
dec
)
Value
CnfLen.DigitalOut
Access
Read
Description
Number of digital output bits in the process image
Table 150: Register address 0x1025
Register address 0x1025 (4133
dec
)
Value
CnfLen.DigitalInp
Access
Read
Description
Number of digital input bits in the process image
Pos: 109.40 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/Zugriff auf Registerwerte - Konfigurationsregister 0x1028 (x41) @ 4\mod_1235635808625_21.doc @ 27808 @ @ 1
Table 151: Register address 0x1028
Register address 0x1028 (4136
dec
)
Value
Boot options
Access
Read/write
Description
Boot configuration:
1: BootP
2: DHCP
4: EEPROM
Pos: 109.41 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/MODBUS/Zugriff auf Registerwerte - Konfigurationsregister 0x1029 (x41) @ 4\mod_1235635910031_21.doc @ 27811 @ @ 1