116 Commissioning
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Pos: 80.19.1 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/IP-Adresse mit DHCP vergeben - Überschrift 3, Die Beschr umfasst folg Arbeitsschritte, Ü4 DHCP aktiv @ 5\mod_1244201774491_21.doc @ 35007 @ 3 @ 1
8.2.2
Assigning IP Address via DHCP
If you want to use DHCP to assign the IP address, it happens automatically via a
DHCP server on the network.
Pos: 80.19.2 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/IP-Adresse mit DHCP vergeben Teil 2 @ 9\mod_1282136848186_21.doc @ 63897 @ 4 @ 1
Note
Total network failure when there are two DHCP servers in the network!
To prevent network failure, never connect a PC, on which a DHCP server is
installed, to a global network. In larger networks, there is usually a DHCP server
already that can cause collisions and subsequent network failure.
Note
There must be a DHCP server in the network for further configuration!
Install a DHCP server on your client PC in the local network if not already
available. You can download a DHCP server free of charge on the Internet, e.g.,
http://windowspedia.de/dhcp-server_download/.
Note
Assign the client PC a fixed IP address and note common subnet!
Note that the client PC, on which the DHCP server is listed, must have a fixed IP
address and that the fieldbus node and client PC must be in the same subnet.
The following steps are included:
• Enable
DHCP
• Disable
DHCP
8.2.2.1
Enable DHCP
Pos: 80.19.3 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/Hinweis: Für aktive Software-Konfiguration, Adresswahlschalter auf 255 stellen! (DHCP) @ 5\mod_1244202728786_21.doc @ 35010 @ @ 1
Set the address selection switch to 255 for active software configuration!
Set the address selection switch to 255 to disable the DIP switch and to enable
DHCP.
Restart the fieldbus node after adjusting the address selection switch to apply the
configuration changes.
Pos: 80.19.4 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/DHCP muss aktiviert sein, Automatische IP-Vergabe durch DHCP (ohne Ethernet-Settings)(352, 882, 881) @ 9\mod_1282138405449_21.doc @ 63904 @ @ 1