WAGO-I/O-SYSTEM 750
Commissioning 115
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Information
More information about changing the static base address
You can also change the base address currently saved in the fieldbus controller as
required.
Proceed as described in the following section "Assigning IP Address via Web
Server".
Pos: 80.17.3 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Feldbusknoten in Betrieb nehmen/IP-Adresse mit dem Adresswahlschalter vergeben - Schritte 1-3 @ 5\mod_1243949663207_21.doc @ 34687 @ @ 1
1.
To configure the IP address via the address selection switch by setting the
host ID (last position of the IP address) to a value that does not equal 0/255,
first convert the host ID to the binary representation.
For example, host ID 50 results in a binary code of 00110010.
2.
Set the bits in sequence using the 8 address switches. Start with address
switch 1 to set bit 0 (LSB) and end with address switch 8 for bit 7 (MSB).
0
0
1
1
0
0
1
O
N
O
FF
8
7
6
5
4
3
2
1
0
Figure 49: Address selection switch
3.
Restart the fieldbus coupler after adjusting the address selection switch to
apply the configuration changes.