106 Function Description
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Table 39: Possible errors during the restore function
Possible error
Procedure
Error message
Solution
No /copy/ and
/settings/ directories on
the memory card
Fieldbus controller is
working as if no
memory card were
present.
No message.
If memory card use is
desired, map the
directory structure of
the internal drive under
/copy/ on the memory
card on the PC.
Then restart the
fieldbus controller.
Manual interrupt
If the /copy/ directory
has not yet been copied
in full, then the copy
process is stopped on
manual interrupt. The
data is incomplete.
Blink code of the I/O
LED
for 30 seconds (error
code 14, error
argument 2) or until the
error is eliminated.
Restart system.
Internal file system is
full
As much data is copied
until the file system is
full.
The copy function is
cancelled. The data is
incomplete.
Blink code of the I/O
LED
(error code 14, error
argument 3) until the
error is eliminated.
Check internal file
system and /copy/
directory on the
memory card and if
necessary, delete files
(e.g. through FTP,
formatting internal
drive or cleaning the
memory card on the
PC).
General internal error
The copy function is
cancelled. The data is
incomplete.
Blink code of the I/O
LED
(error code 14, error
argument 7).
If necessary, restart
function and device.
The file size may not be larger than the size of the internal drive!
Note that the amount of data in the /copy/ directory may not exceed the total size
of the internal drive.