32 • Simulation
Simulating Telecontrol via Ethernet (TCP/IP) with the WinPP104 Program
WAGO-I/O-SYSTEM
750
Telecontrol Quick-Start Manual
The settings are incorporated into the program by pressing the "OK" button.
The simulation can be started by clicking the
button.
All signals from the outstation (WAGO Controller 750-872) to the central
processor (PC) are now displayed when their values change.
Commands from the central processor to the station can be simulated. These
can be executed under "Parameter setting"
Æ
"Telegrams“
Æ
"B individual
command with date ...".
Fig. 32: Parameterizing a command WinPP104
In the newly started window the "Type" must be set to "45=Individual
command“ and "2 Command recognition" must be set to "3" (continuous
command).
Command recognition can be set from "0" - "31". The values "1" = short, "2"
= long and "3" = continuous are of interest for individual commands. The time
is set in CoDeSys on the "Resources" tab under "Controller configuration“
Æ
highlight "IEC 60870-5 config [VAR]“
Æ
highlight "IEC 60870
configuration" on the right-hand side under "Execution time".
The station and object address can be seen from CoDeSys on the "Resources"
tab under "Controller configuration“
Æ
highlight "IEC 60870-5 config
[VAR]“ on the right-hand side.
In this case it is the No. 65793 from the command "IEC870_45C_SC_NA
(001.001.001 = 65793)".